国家电网公司物资采购标准(2009年版) (10kV一次设备交流变压器卷(第二批) 10kV变压器册)
10kV三相油浸式变压器专用技术规范 (编号:1001002-0010-01)
目 次
1 标准技术参数表 ·········································································································································· 2 项目需求部分 ············································································································································· 2.1 图纸资料提交单位 ···································································································································· 2.2 工程概况 ················································································································································· 2.3 使用条件 ················································································································································· 2.4 可选技术参数表 ········································································································································ 2.5 项目单位技术差异表 ································································································································· 3 投标人提供信息 ·········································································································································· 3.1 投标人技术偏差表 ···································································································································· 3.2 投标人应提供的其他资料 ···························································································································
1 标准技术参数表
投标人应认真逐项填写技术参数和性能要求响应表中投标人保证值,不能空格,也不能以“响应”两字代替,不允许改动招标人要求值。如有偏差,应填写技术偏差表。“投标人保证值”应与型式试验报告相符。
表1 技术参数和性能要求响应表
序号 一 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 二 1 2 3 4 三 1 2 3 4 四 五 100%额定电压时 额定频率额定电压时空载损耗 顶层油 绕组(平均) 绕组(热点) 铁心、油箱及结构表面 空载损耗 kW 空载电流 % 见附表1 (投标人填写) 见附表1 (投标人填写) K 高压绕组雷电全波冲击电压(峰值) 高压绕组雷电截波冲击电压(峰值) 高压绕组额定短时工频耐受电压(有效值) 低压绕组额定短时工频耐受电压(有效值) 变压器型号 铁心材质 铁心结构 高压绕组 低压绕组 联结组 额定频率 额定容量 相数 调压方式 调压位置 调压范围 中性点接地方式 冷却方式 磁通密度 名 称 单位 额定值 kV kV Hz kVA T 绝缘水平 kV kV kV 温升限值 55 65 78 75 (投标人填写) (投标人填写) (投标人填写) (投标人填写) 75 85 35 5 (投标人填写) (投标人填写) (投标人填写) (投标人填写) 见表6 冷轧取向硅钢片 见表6 见附表1 0.4 见附表1 50 见附表1 3 见附表1 高压侧 见附表1 不接地 ONAN (投标人提供) (投标人填写) (投标人填写) (投标人填写) (投标人填写) (投标人填写) (投标人填写) (投标人填写) (投标人填写) (投标人填写) (投标人填写) (投标人填写) (投标人填写) (投标人填写) (投标人填写) (投标人填写) 标准参数值 投标人保证值
表1(续)
序号 六 七 八 起始负荷80%,环境温度40℃下过载能力(过负荷能力及持续运行时间) 温升按照长期急救周期性负载温度 限值控制 主分接 噪声水平 名 称 单位 负载损耗 kW、75℃ dB 负载能力 见附表1 见附表2 (投标人填写) (投标人填写) 标准参数值 投标人保证值 过载倍数 持续运行时间(h) 1.5 (投标人填写) 2 (投标人填写) 九 1 2 3 4 十 十一 1 2 十二 1 2 3 4 5 6 7 8 9 10 11 12 相—地 1.05 1.1 1.25 1.9 2.0 相—相 1.05 1.1 1.25 1.5 1.58 释放压力 回复压力 器身质量 油质量 总质量 变压器运输时允许的最大倾斜度 10kV套管有效爬距 t t t 质量 (投标人提供) (投标人提供) (投标人提供) 15° >300 (投标人填写) (投标人填写) (投标人填写) (投标人填写) (投标人填写) mm 压力释放装置 MPa MPa 工频过电压倍数 空载持续 时间 连续 连续 20s — — 空载持续 时间 连续 连续 — — (投标人提供) (投标人提供) (投标人填写) (投标人填写) 满载持续 时间 连续 20min 20s 1s 0.1s 满载持续 时间 连续 20min 20s 1s 0.1s (投标人填写) (投标人填写) (投标人填写) (投标人填写) (投标人填写) (投标人填写) (投标人填写) (投标人填写) (投标人填写) (投标人填写) (投标人填写) (投标人填写)
附表1 标准参数表
变压器 容量 (kVA) 50 100 160 200 315 400 630 800 200 315 400 630 有载 ±4×2.5% 0.4 Dyn11 Yyn0 无励磁 10 10.5 ±5 ±2×2.5% 0.4 Dyn11 Yyn0 调压 方式 高压 (kV) 高压分接 范围 低压 (kV) 联结组 标号 空载损耗 (kW) 0.13 0.20 0.28 0.34 0.48 0.57 0.81 0.98 0.38 0. 0. 0.96 负载损耗 (kW) 0.91/0.87 1.58/1.50 2.31/2.2 2.73/2.6 3.83/3.65 4.52/4.30 6.20 7.50 2.91 4.10 4.96 7.27 4.5 4.0 4.5 4.0 短路阻抗 (%) 注 对于额定容量为500kVA及以下的变压器,表中斜线上方的负载损耗值适用于Dyn11联结组,斜线下方的负载
损耗值适用于Yyn0联结组。
附表2 噪 声 水 平
变压器容量(kVA) 50 100 160 200 315 400 630 800 轨距A×B(mm×mm) 400×400 400×450 550×550 550×550 660×650 660×750 660×850 660×850 噪声水平(dB) 50 52 56 58 58 60 62 2 项目需求部分
货物需求及供货范围一览表见表2。必备的备品备件、专用工具和仪器仪表供货表见表3。
表2 货物需求及供货范围一览表
项目单位要求 序号 变压器型号 1 2 3 4 主要参数 单位 数量 变压器型号 主要参数 单位 数量 投标人响应
表3 必备的备品备件、专用工具和仪器仪表供货表
项目单位要求 序号 1 2 3 名 称 单 位 型号和规格 数量 型号和规格 数量 投标人响应 2.1 图纸资料提交单位
需确认的图纸资料应由卖方提交到表4所列的单位。
表4 卖方提交的需经确认的图纸资料及其接收单位
提交图纸、资料名称 认可图、最终图 (附电子文档) 认可图、最终图 说明书 试验报告 (附电子文档) 接收图纸单位名称、地址、邮编、电话 (设计单位) 提交份数 (项目单位) 2.2 工程概况
2.2.1 项目名称: 。 2.2.2 项目单位: 。 2.2.3 交通、运输: 。 2.3 使用条件
使用条件参数表见表5。
表5 使用条件参数表
序号 1 2 3 4 5 6 名 称 额定电压 最高运行电压 系统中性点接地方式 额定频率 污秽等级 系统短路电流水平(高压侧) 最高日温度 ℃ 最低日温度 7 环境温度 最大日温差 最热月平均温度 ℃ 最高年平均温度 日相对湿度平均值 8 湿度 % 月相对湿度平均值 ≤90 K 单位 kV kV Hz kA 招标人要求值 10 12 不接地 50 Ⅲ 20 40 25 25 +30 +20 ≤95
表5(续)
序号 9 10 11 12 13 14 名 称 海拔 太阳辐射强度 最大覆冰厚度 离地面高10m处,维持10min的平均最大风速 地面水平加速度 耐受地震能力 正弦共振三个周期安全系数 单位 m W∕cm2 mm m/s m/s2 招标人要求值 ≤1000 0.1 20 35 2 ≥1.67 (项目单位提供) 安装场所(户内/外) 注 1. 环境最低气温超过25℃的需要进行温度修正。
2. 污秽等级为Ⅳ级的需提供该地区的污秽等级图。 3. 有关海拔、污秽、温度的修正情况见表7。
2.4 可选技术参数表
可选技术参数表见表6。
表6 可选技术参数表
序号及 名称 1 2 3 4 5 „ 项 目 变压器型号 铁心结构 联结组 调压方式 高压分接范围 标准参数值 卷铁心、叠铁心 Dyn11或Yyn0 无励磁、有载 ±5%或 ±2×2.5% 招标人要求值 (项目单位提供) (项目单位提供) (项目单位提供) (项目单位提供) (项目单位提供) 投标人保证值 (投标人填写) (投标人填写) (投标人填写) (投标人填写) (投标人填写) 2.5 项目单位技术差异表
项目单位原则上不能改动通用部分条款及专用部分固化的参数,根据工程实际情况,使用条件及相关技术参数如有差异,应逐项在项目单位技术差异表中列出。
表7 项目单位技术差异表(项目单位填写)
(本表是对技术规范的补充和修改,如有冲突,应以本表为准)
序号 1 2 „ 序号 1 2 „ 项 目 „„ 项 目 „„ 标准参数值 变更条款页码、款号 项目单位要求值 原表达 投标人保证值 变更后表达
3 投标人提供信息
投标人应提供的信息见表8~表10。
表8 销售运行业绩表
序号 1 2 3 4 5 6 7 型号规格 数量 用户单位 用户联系人 用户联系人电话 投运时间 备注 表9 推荐的备品备件、专用工具和仪器仪表供货表(投标人填写)
序号 1 2 3 4 5 6 名 称 型号和规格 单位 数量 表10 主要部件材料表
序号 1 2 3 4 5 6 7 8 9 10 11 12 13 „ 名 称 硅钢片 变压器油 线圈导线 密封件 分接开关 高压套管 低压套管 储油柜 气体继电器 油位计 油温度计 压力释放阀 其他需要说明的材料及附件 型号、规格、厂家、原产地 招标人要求 投标人响应 备 注 3.1 投标人技术偏差表
投标人提供的产品技术规范应完全满足本招标文件中的规定。若有偏差,投标人应如实、认真地在技术偏差表(见表11)中填写偏差值,否则视为与本招标文件中规定的要求一致。若无技术偏差,则应在技术偏差表中填写“无偏差”。
表11 投标人技术偏差表
序号 1 2 3 项 目 对应条款编号 技术招标文件要求 差 异 备 注 3.2 投标人应提供的其他资料 3.2.1 用户运行证明。
3.2.2 同类产品鉴定证书及鉴定产品的型式试验报告(见表12和表13)。
表12 投标人提供的鉴定证书表
序号 鉴定产品型号名称 组织鉴定单位 依据标准 鉴定时间 表13 投标人提供的试验检测报告表
序号 产品型号名称 试验报告类别和 内容 依据标准 试验时间 试验单位 3.2.3 投标人需提供的设备图纸及资料
投标文件中投标人应提供以下图纸及资料: 1) 说明书。 2) 试验报告。
因篇幅问题不能全部显示,请点此查看更多更全内容